Fire Alarm & Fire Survival Cables

Fire Alarm & Fire Survival Cables

Fire alarm cables for highest safety requirements
Applications
Cables to maintain power supplies and data transmission to fire alarm system,public adress and voice alarm systems.

Indoor for:
Audio Circuits
Control Circuits
Initiating Circuits
Notification Circuits

FIRE ALARM CABLES (300 V)

Construction:

Solid/Stranded plain copper conductor, PVC insulation, metallic barrier, tinned copper earth conductor & FRLS PVC Sheathed.

Part No. Cores × mm² Colour O/D (mm)
PSFRS215R 2 × 1.5 Red 7.7
PSFRS215W 2 × 1.5 White 7.7
PSFRS415R 4 × 1.5 Red 9.2
PSFRS415W 4 × 1.5 White 9.2
PSFRS225R 2 × 2.5 Red 8.9
PSFRS225W 2 × 2.5 White 8.9
PSFRS425R 4 × 2.5 Red 10.9
PSFRS425W 4 × 2.5 White 10.9

FIRE SURVIVAL CABLES

It is now recognised that in some buildings the continued functioning or circuit integrity of some cables are essential in providing sufficient time for evacuation.
These Enhanced version cables shown below are suitable for installation where evacuation may be
delayed, for example in hospitals or high-rise buildings without sprinklers. The ‘enhanced’ group of
cables offer a viable alternative to MICC (Mineral Insulated Copper Clad) in many applications with the
benefit of faster installation and easier routing.
These collection of cables are also popular on overground railways, other transport systems and other ommercial applications where fire and smoke propagation are critical factors.
Applications range from radio communications to alarm and emergency evacuation circuits.

Construction:

Solid plain copper conductor, Mica tape, silicone rubber insulation, metallic barrier, tinned
copper earth conductor & enhanced low smoke halogen free sheath.

Part No. Cores × mm² Colour O/D (mm)
PSFSS215R 2 × 1.5 Red 8.6
PSFSS215W 2 × 1.5 White 8.6
PSFSS415R 4 × 1.5 Red 10.1
PSFSS415W 4 × 1.5 White 10.1
PSFSS225R 2 × 2.5 Red 9.9
PSFSS225W 2 × 2.5 White 9.9
PSFSS425R 4 × 2.5 Red 11.9
PSFSS425W 4 × 2.5 White 11.9
Standards As Per
BS 5839-1:2002 Clause 26.2(e) Enhanced
BS 8434-2:2003
BS EN 50200 PH120
BS 6387 C, W & Z
IEC 60332-3
IEC 60332-1
BS EN 50265
BS EN 50266
IEC 60754
BS EN 50267
IEC 61034
BS EN 50268

Our Products