Single Core Fire Survival cables
- Home
- Single Core Fire Survival cables
Single Core Fire Survival cables
Parashield Single Core Fire Survivaly Cable is designed for fixed installation s where circuit integrity is critical in the event of a fire The Low Smoke Halogen Free insulation also ensures minimal fumes and smoke are given Inff providing safety for both personnel and property.
Construction:
Stranded plain copper conductor to Class 2, mica tape & LSHF insulation.
Technical Data:
Voltage Rating– 0.6/1KV
Temperature Rating- -40°C to +90°C
Minimum Bending Radius- -40°C to +90°C
| Parameter | Specification |
|---|---|
| Flame Retardant | IEC 60332-1-21, IEC 60332-3-24 Category C |
| Smoke Emission | IEC 61034-2 |
| Halogen Emission | IEC 60754-1 & 2, EN 50267-2-1 |
| Fire Resistant |
BS 6387 Categories CWZ
(when applied to a single cable appropriately protected in steel conduit) |
| Sheath Color | Different colors as per customer requirement |
| Part No. | Size (mm²) | No. of Strands / mm | Conductor Resistance at 20°C (Ω/km) | Approx. Weight (Kg/Km) |
|---|---|---|---|---|
| PSFS11500 | 1.50 | 7/0.53 | 12.10 | 31 |
| PSES1260 | 2.50 | 7/0.67 | 7.41 | 41 |
| PSES1400 | 4.00 | 7/0.85 | 4.61 | 54 |
| PSFS1800 | 6.00 | 7/1.04 | 3.08 | 84 |
| PSES110 | 10.00 | 7/1.35 | 1.83 | 144 |
| PSES116 | 16.00 | 7/1.70 | 1.15 | 195 |
| PSFS125 | 25.00 | 7/2.14 | 0.73 | 315 |
| PSFS135 | 35.00 | 7/2.52 | 0.52 | 405 |
| PSFS150 | 50.00 | 19/1.78 | 0.39 | 543 |
| PSFS170 | 70.00 | 19/2.14 | 0.27 | 761 |
| PSFS195 | 95.00 | 19/2.52 | 0.19 | 1120 |
| PSFS1120 | 120.00 | 37/2.03 | 0.15 | 1390 |
| PSFS1150 | 150.00 | 37/2.25 | 0.12 | 1692 |
| PSFS1185 | 185.00 | 37/2.52 | 0.10 | 2108 |
| PSFS1240 | 240.00 | 61/2.25 | 0.08 | 2854 |
| PSFS1300 | 300.00 | 61/2.52 | 0.06 | 3464 |